Insulation and Fire Resisting Ductwork
Oct 03, 2019

Mechanical Ventilation in a building is an essential part of creating comfortable conditions for the occupants. There is an entire science involved: too much air can lead to higher energy bills, too little and we can create dampness and unhealthy zones!

Ventilation also has an impact on our primary fire safety strategy, compartmentation. The use of ducts can create potential consequences in a fire that can inhibit safe evacuation and make fires more difficult to contain and control.

There are 5 scenarios we need to consider

  • 1. General ventilation ducts

    General ventilation ducts have no fire resisting properties. They depend on the use of fire dampers to EN1366-2 when crossing fire compartments. The fire damper will close in the event of a fire and secure the compartment.

  • 2. Ducts for the purpose of removing smoke from a fire

    Ducts for the purpose of removing smoke are the subject of a classification report EN13501-4. This report is provided by a notified body, following a review of the tests conducted to EN1366-1 and EN1366-8 or 9. EN1366-9 ducts are only suitable for single fire compartment applications. They are tested to 600°C. EN1366-8 is a test for multi-compartment ducts and is subject to the full hydrocarbon fire curve, and must be tested with Insulation. Uniquely, the results for the insulation’s performance comes from the EN1366-1 tests.


    Both the ductwork and the insulation are subject to the test. They are not treated as individual items, but as a complete system. So why the insulation? When we exhaust smoke/hot gases from the scene of a fire, and cross another fire compartment before reaching atmosphere (outside), we run the risk of a flashover event. The cause of a flashover, the most common type being a hot rich flashover, is thermal radiation feedback. Inside a structure the hot gases radiate heat, and when the area through which it passes has been saturated with the energy (heat), components break down and flames may break out almost at once over all of the surfaces within that heated environment. Smoke ducts to EN13501-4 multi-compartment are insulated to prevent flashover, and thus prevent secondary fires.

  • 3. Ducts used to remove odours from the kitchen

    Ducts used in kitchen scenarios also have a fire risk, specifically through the presence of grease. Because of oxidisation, the grease has a flash temperature of 180°C, considerably lower than oils used in cooking. Where the ductwork is multi-compartment, there is a risk that a fire in a compartment (other than the kitchen) could reach the kitchen extract. This would cause the grease to ignite and the fire to cascade through all compartments with the kitchen extract passing through them. The ducts are classified to EN13501-3 and tested to EN1366-1. Multi-compartment kitchen extracts require insulation to prevent the flames on the outside, causing the grease on the inside to ignite. In the fire test EN1366-1, a measurement called combustible linings is taken. In this test, an A duct has thermocouples placed inside the duct, inside the furnace, and a measurement is taken of the temperature rise of the ductwork. The duct is tested with insulation and mechanical pressure of -500 PA. The outcome of these measurements is often referred to as the kitchen extract result. Again it is a combination of the metal duct and the insulation that provides the result. Changing the duct construction or insulation used will deliver different unproven results.

  • 4. Ducts for the pressurisation of escape areas

    Pressurisation ducts are used to keep smoke from penetrating certain critical areas of a building by maintaining higher pressure differentials than normal areas. Smoke inhibits escape and firefighting. A pressurised system is a special form of mechanical ventilation system. Fire dampers cannot be used in such systems. The ductwork is again tested to EN 1366-1 and classified to EN13501-3. Pressurisation ducts are Insulated to prevent heat entering the protected areas.

  • 5. Ducts used where fire dampers are not suitable (passive)

    Passive ducts are used to provide a natural air flow. In many instances they do not contain fire dampers where maintenance and testing could be problematic. Such ducts need to be classified to EN13501-3 and tested to EN1366-1. Passive ducts do not have a mechanical element. In the event of a fire, no air movement is driven in the ducts, and so the ductwork may not require insulation. Where a passive duct traverses an EI wall, the fire designer may require the duct to maintain the I (Insulation) performance of the wall, and may need the duct insulated.

Of special attention are areas where fire ductwork is used and it crosses a protected route or lobby. The element of the duct crossing these areas must have the integrity from EN13501-3 and also insulation. This is to offer protection to those using these areas in the event of a fire.


Historically, we didn’t give much attention to the need for insulation properties. However, as our understanding of fire risk has developed, insulation is seen as critical in preventing secondary fires during an incident. The standards and particularly the classification reports EN13501-4 and EN13501-3 have defined the system as being critical. The combination of ducts and insulation in tests, have revealed the importance of both elements contributing to providing the EI S classifications (E = Integrity, I = Insulation, S = leakage).


Thor Duct® has been tested extensively with uninsulated and insulated solutions. This ensures a safe solution for every fire scenario. As our industry evolves, we will continue to channel this knowledge to our clients, and test and prove the full suite of Thor Duct® products to ensure our clients are getting the safest, most compliant solutions available.

Need To Know More?


     Contact us today to find more about training and CPD from Thor Duct®.


CPD Enquiry
Thor Duct 2.0 development and testing completion
by RG329912 29 May, 2023
Michael Renaghan FCCA, Technical lead at Thor Duct ® , would like to express his gratitude to the team of Swedish (Ola Berg, Jesper Karlsson), Italian (Enrico Audisio), and Irish colleague (Barry Murphy and all the management at Lindab Ireland) for their successful completion of the development and testing phase of Thor Duct ® 2.0 , the company's latest product offering.
Lindab Acquires Thor Duct
08 Jun, 2020
Lindab has acquired IP rights, customer contracts and supplier agreements for Thor Duct ‘s fire ductwork system. Thor Duct is based in Ireland and is licensing the production of its certified technology to a number of customers in the UK and Ireland, including Lindab. The acquisition includes customer contracts to a value of EUR 2 million and is a spin-off from current operations. The acquisition will add a positive contribution to Lindab’s profitability.
Standards Alone Don’t Guarantee Good Outcomes
31 Oct, 2019
The introduction by the European Committee for Standardisation, (CEN) of a series of standards covering the placing on the European market of ducts for fire and smoke management, has set the bar for product safety. Compliance with the standards ensures they are fit for purpose, and perform as intended when called into action.
What’s the maximum size EN ducts and how do you specify them?
23 Aug, 2019
In order to determine the maximum size permitted on the market as a certified product, the test standards are the critical document.
Why Insulation Is Never Enough
by RG329912 07 May, 2019
Fixing insulation to ductwork ignores the importance of a proven Integrity classification for the ductwork.
Reposition Your Manufacturing Business With Thor Duct
09 Jan, 2019
As fire strategy evolves, it is becoming a feature of every ductwork package to have an element of smoke, kitchen and fire ductwork incorporated into the package.
How Lindab Thor Duct Launched Mersey Vent Growth Spurt
08 Jan, 2019
In our experience local markets need local suppliers, people they are comfortable with and trust. To this end, we have developed a licencing model for Thor Duct.
Training & Education
08 Jan, 2019
Most people have heard of new EN standards notably 12101-7, 1366-1 and 1366-8, but unfortunately many haven’t quite grasped their significance.
Share by: